Code: 6181 Y CU
CU: IEC 60228 CLASS 1 & 2
U: Solid Conductor
R: Stranded Conductor
Standarts
BS 6004
Technical Data
Max operating temperature: 70 0C
Short circuit temperature: 160 0C ( max. 5 sn. )
Rated Voltage : 300 / 500 V
Application
Used in fixed installation in dry and damp places, on and under plaster for domestic and light industrial wiring.
Construction:
1- Solid or stranded copper conductor
2- Double PVC insulation
BOYUT VE AĞIRLIKLAR ( DIMENSIONS AND WEIGHTS ) |
ELEKTRİKSEL ÖZELLİKLER
(ELECTRICAL PROPERTIES) |
||||
Tip
Type |
Nominal Kesit
Nominal cross-section |
Dış Çap (Yaklaşık)
Overall Diameter (approx.) |
Net Ağırlık (yaklaşık)
Net wieght (apprx.) |
İletken DC Direnci 20 0C'de max.
DC Condusctor Resistance at 20 0C |
Akım Taşıma Kapasitesi
Current Carrying Capacity |
Havada 30 0C'de
In Air at 30 0C
|
|||||
mm2 |
mm |
kg/km |
ohm/km |
A |
|
1,00 | 4,2 | 28 | 18,10 | 19 | |
6181 Y | 1,5 | 4,60 | 36 | 12,10 | 31 |
2,5 | 5,20 | 50 | 7,41 | 43 | |
4 | 6,10 | 73 | 4,61 | 56 | |
6 | 6,70 | 96 | 3,08 | 71 | |
10 | 7,90 | 146 | 1,83 | 97 | |
16 | 9,20 | 215 | 1,15 | 130 | |
25 | 10,70 | 323 | 0,727 | 171 | |
35 | 11,80 | 417 | 0,524 | 210 |