YE3V-YXV-2XY CU

Code: YE3V-YXV-2XY CU

CU: IEC 60228 CLASS 1 & 2

U: Solid Conductor

R: Stranded Conductor

Standarts

IEC 60 502-1 VDE 0276-603

Technical Data

Max operating temperature: 90 0

Short circuit temperature: 250 0C ( max. 5 sn. )

Rated Voltage : 0,6 / 1Kv 

Application

Used as energy, utility and lighting cables for outdoor installations underground or in cable ducts. It is suitable for high temperature conditions and also it provides better insulation.

Construction:

1- Solid or stranded  copper conductor

2- XLPE insulation

3- PVC sheath

 

BOYUT VE AĞIRLIKLAR

( DIMENSIONS AND WEIGHTS )

ELEKTRİKSEL ÖZELLİKLER

(ELECTRICAL PROPERTIES)

Tip

Type

Nominal Kesit

Nominal cross-section

Dış Çap (Yaklaşık)

Overall Diameter (approx.)

Net Ağırlık (yaklaşık)

Net wieght (apprx.)

İletken DC Direnci 20 0C'de max.

DC Condusctor Resistance at 20 0C

Akım Taşıma Kapasitesi

Current Carrying Capacity

Toprakta 20 0C'de

In ground at 20 0C

Havada 30 0C'de

In Air at 30 0C

 

 

mm2

mm

kg/km

ohm/km

OOO

O°O

OOO

O°O
                 
N2XY 1x1,5 5,6 47 12,10 - - - -
1x2,5 5,95 59 7,41 - - - -
1x4 7 85 4,61 - - 64 46
1x6 7,5 105 3,08 - - 79 58
1x10 8 145 1,83 - - 106 79
1x16 8,5 210 1,15 139 115 128 102
1x25 11 300 0,727 179 149 173 139
1x35 12 400 0,524 213 178 212 170
1x50 12,5 550 0,387 251 211 258 208
1x70 15,5 750 0,268 307 259 328 265
1x95 17 1000 0,193 366 310 404 326
1x120 19 1200 0,153 416 352 471 381
1x150 21 1500 0,124 465 396 541 438
1x185 23 1900 0,0991 526 449 626 507
1x240 26 2450 0,0754 610 521 749 606