Code: NVV-NYM-05VV-U CU
CU: IEC 60228 CLASS 1 & 2
U: Solid Conductor
R: Stranded Conductor
Standarts
TSE 9759 HD 21.4.S2-VDE 0250-204
Technical Data
Max operating temperature: 70 0C
Short circuit temperature: 160 0C ( max. 5 sn. )
Rated Voltage : 450 / 750 V
Application
Used for fixed wiring in dry and dump premises, in conduits on and under plaster, can not be used for under ground laying.
Construction:
1- Solid or stranded copper conductor
2- PVC insulation
3- PVC filter
2- PVC sheath
BOYUT VE AĞIRLIKLAR ( DIMENSIONS AND WEIGHTS ) |
ELEKTRİKSEL ÖZELLİKLER
(ELECTRICAL PROPERTIES) |
||||
Tip
Type |
Nominal Kesit
Nominal cross-section |
Dış Çap (Yaklaşık)
Overall Diameter (approx.) |
Net Ağırlık (yaklaşık)
Net wieght (apprx.) |
İletken DC Direnci 20 0C'de max.
DC Condusctor Resistance at 20 0C |
Akım Taşıma Kapasitesi
Current Carrying Capacity |
Havada 30 0C'de
In Air at 30 0C
|
|||||
mm2 |
mm |
kg/km |
ohm/km |
A |
|
NYM | |||||
2x1,5 | 8,60 | 119,95 | 12,1 | 18 | |
2x2,5 | 9,88 | 155,17 | 7,41 | 26 | |
2x4 | 10,69 | 199,12 | 4,61 | 34 | |
2x6 | 11,75 | 260,56 | 3,08 | 44 | |
2x10 | 15,51 | 444,41 | 1,83 | 61 | |
2x16 | 18,12 | 627,01 | 1,15 | 82 | |
2x25 | 21,8 | 940 | 0,727 | 108 | |
2x35 | 23,7 | 1163,81 | 0,524 | 135 | |
3x1,5 | 9,05 | 135,52 | 12,1 | 18 | |
3x2,5 | 10,36 | 181,36 | 7,41 | 26 | |
3x4 | 11,27 | 244,27 | 4,61 | 34 | |
3x6 | 13,02 | 347,47 | 3,08 | 44 | |
3x10 | 16,71 | 554,7 | 1,83 | 61 | |
3x16 | 19,38 | 876 | 1,15 | 82 | |
3x25 | 24,47 | 1273 | 0,727 | 108 | |
3x35 | 24,85 | 1524,15 | 0,524 | 135 | |
4x1,5 | 9,90 | 163,5 | 12,1 | 18 | |
4x2,5 | 11,27 | 224,79 | 7,41 | 26 | |
4x4 | 12,72 | 313,22 | 4,61 | 34 | |
4x6 | 14,93 | 436,1 | 3,08 | 44 | |
4x10 | 18,58 | 684,76 | 1,83 | 61 | |
4x16 | 21,44 | 1074 | 1,15 | 82 | |
4x25 | 25,8 | 1581 | 0,727 | 108 | |
4x35 | 28,2 | 1891 | 0,524 | 135 |