YVV-NYY CU

Code: YVV-NYY CU

CU: IEC 60228 CLASS 1 & 2

U: Solid Conductor

R: Stranded Conductor

Standarts

IEC 60 502-1 VDE 0271-0276

Technical Data

Max operating temperature: 70 0

Short circuit temperature: 160 0C ( max. 5 sn. )

Rated Voltage : 0,6 / 1Kv 

Application

Used as power cables where mechanical damage is unexpected indoors, under ground, in cable ducts and industrial plants.

Construction:

1- Solid or stranded  copper conductor

2- PVC insulation

3- PVC filter

2- PVC sheath

 

BOYUT VE AĞIRLIKLAR

( DIMENSIONS AND WEIGHTS )

ELEKTRİKSEL ÖZELLİKLER

(ELECTRICAL PROPERTIES)

Tip

Type

Nominal Kesit

Nominal cross-section

Dış Çap (Yaklaşık)

Overall Diameter (approx.)

Net Ağırlık (yaklaşık)

Net wieght (apprx.)

İletken DC Direnci 20 0C'de max.

DC Condusctor Resistance at 20 0C

Akım Taşıma Kapasitesi

Current Carrying Capacity

Toprakta 20 0C'de

In ground at 20 0C

Havada 30 0C'de

In Air at 30 0C

 

 

mm2

mm

kg/km

ohm/km

A

A

             
NYY 4x1,5 11,5 204,79 12,1 26 18,5
4x2,5 12,78 284,21 7,41 34 25
4x4 14,31 354,76 4,61 44 34
4x6 15,97 471,39 3,08 56 43
4x10 19,77 692,29 1,83 75 60
4x16 22,21 1010 1,15 98 80
4x25 26,24 1030,44 0,727 128 106
4x35 28,76 1918,23 0,524 157 131
4x50 31,6 2570 0,387 185 159
4x70 36 3560 0,268 228 202
4x95 41 4740 0,193 275 244
4x120 46 5770 0,153 313 282
4x150 51,7 7160 0,124 353 324
4x185 56 8800 0,0991 399 371
4x240 63 11600 0,0754 464 436