Code: NYIFY CU
CU: IEC 60228 CLASS 1 & 2
U: Solid Conductor
R: Stranded Conductor
Standarts
DIN VDE 0250-201
Technical Data
Max operating temperature: 70 0C
Short circuit temperature: 160 0C ( max. 5 sn. )
Rated Voltage : 230 / 400 V
Application
Used for fixed dry and damp premises on and under plaster for permanent installation. They can not be used for underground ltying.
Construction:
1- Solid or stranded copper conductor
2- PVC insulation
2- PVC sheath
BOYUT VE AĞIRLIKLAR ( DIMENSIONS AND WEIGHTS ) |
ELEKTRİKSEL ÖZELLİKLER
(ELECTRICAL PROPERTIES) |
||||
Tip
Type |
Nominal Kesit
Nominal cross-section |
Dış Çap (Yaklaşık)
Overall Diameter (approx.) |
Net Ağırlık (yaklaşık)
Net wieght (apprx.) |
İletken DC Direnci 20 0C'de max.
DC Condusctor Resistance at 20 0C |
Akım Taşıma Kapasitesi
Current Carrying Capacity |
Havada 30 0C'de
In Air at 30 0C
|
|||||
mm2 |
mm |
kg/km |
ohm/km |
A |
|
NYIFY | |||||
2x1 | 3,68x12,66 | 74,59 | 12,1 | 18 | |
2x2,5 | 4,17x13,30 | 87,94 | 7,41 | 26 | |
2x4 | 5,13x14,03 | 125 | 4,61 | 34 | |
3x1,5 | 3,75x18,37 | 91 | 12,1 | 18 | |
3x2,5 | 4,7x19,6 | 135 | 7,41 | 26 | |
3x4 | 5,3x21,4 | 187 | 4,61 | 34 | |
4x1,5 | 3,9x25,5 | 135 | 12,1 | 18 |